Generator 1250 kVA - Technical File

Generator 1250 kVA

Alternator: Leroy Somer
Motor: Cummins KTA50-G3

1250 kVA

Performance

Primary capacity in kVA. (400V cos.phi 0.8): 1250 Standby power in kVA. (400V cos.phi 0.8): 1471 Variable power at 50 Hz: 230/400 Variable power at 60 Hz: 254/440

Dimensions and weights

Overall Length (mm): 6100 Overall width (mm): 2480 Overall height (mm): 2642 Weight with empty fuel tank (kg): 16300 Weight with full fuel tank (kg): 17420

Fuel

Content internal double-walled fuel tank (liters): 1500 Fuel consumption per hour at full load (liter): 207,3 Maximum number of operating hours at full load with full internal fuel tank (hours): 6,3 3-way fuel crane (switch internal / external tank): Std

Features

generator excitation type (special AREP wrapped alternator): PMG Insulation class: H2 Digital control: Schneider Masterpact NW20 Voltage regulator (no load to full load): 0,5% Inverter: Electronic Nature Electronic Security:

Safety and Environment

Sound level at 7 meters (-dB (A)): 67 Internal double-walled fuel tank: Std Min.100% fluid containment (complete Insulation against environment): Std TA-Luft conform (completely complies with European safety): Std CE compliant (fully compliant with European safety): Std

Request an inquiry without obligation

Determine your electricity needs

België / Belgique

powersolutions country belgium powersolutions projecten in België powersolutions projets en Belgique

France

powersolutions country france powersolutions projets en France

International

powersolutions country international powersolutions international projects powersolutions proyectos internacionales

Power solutions respects your data privacy.
Why cookies? Simply because they are used to help the website function, to improve your browser experience, to integrate with social media and to show relevant advertisements tailored to your interests. Click 'I understand' to accept cookies and go directly to the site or click more information.

I understand